Prefabricated Substation

Prefabricated Substation

Product Description

YB series prefabricated substations are products produced in compliance with the standards of GB/T17467 "High Voltage/Low Voltage Prefabricated Substations". This product is composed of four parts: housing, transformer, and high-voltage/low-voltage switchgear, and can penetrate deep into the load center. It has the characteristics of small size, beautiful appearance, safety and reliability, and easy installation. It is suitable for outdoor places such as residential areas, factories and mining enterprises, hotels, hospitals, parks, stations, oil fields, airports and temporary facilities.

Service Conditions

  • Ambient Temperature: -30℃ ~ +40℃
  • Altitude Altitude: ≤2000m
  • Relative Humidity: ≤90% (+25℃)
  • Wind speed: ≤35m/s
  • Earthquake intensity Earthquake intensity:
  • Horizontal acceleration Horizontal acceleration: ≤0.4m/s
  • Vertical acceleration: ≤0.2m/s
  • Service environment:
  • Keep away from the follow place: fire, explosion, dirty, chemical etching And strenuous vibra.tion

Structural Style

Product FeaturesProduct Features

  • It has a unique design, compact structure, and is easy to transport and install. For different use environments, it adopts different heat-proof, moisture-proof, and anti-corrosion measures, and can be sprayed with different colors of paint. It has strong anti-corrosion capabilities and is in harmony with the surrounding environment. coordinated.
  • It has a good ventilation and heat dissipation system, which is composed of several natural ventilation channels and fans, and has a novel heat insulation layer to ensure that the product operates under conditions of excessive load and temperature.
  • It has complete monitoring, alarm and protection means, which not only facilitates the maintenance work of patrol personnel, but also ensures the personal safety of personnel.
  • Data Sheet

    serial number project unit High voltage side Transformer Low voltage side
    1 Rated voltage kV 10 10/0.4 0.4
    2 Maximum highest operating voltage kV 12 0.4
    3 Rated Capacity kVA 50~1000
    4 Rated current A ≤630 ≤1600
    5 Rated short circuit breaking current KA 52 30, 50
    6 Rated short-time withstand current KA/s 20/2 30/1
    7 Rated short circuit making current KA 50 63, 105
    8 Rated peak withstand current KA/s 50/0.3 50/0.3
    9 Power frequency withstand voltage kV Isolation fracture: 48
    Phase to phase and relative to ground: 42
    35/28 2.5/2.0
    10 noise level dB Oil change ≤55, dry change ≤65
    11 Number of circuits Unit 3 1 ≤22
    12 Protection level IP34D

    ©2023 CHNSUN ELECTRIC MANUFACTURING CO.,LTD. All rights reserved